Shear Induced Removal of Calcium Carbonate Scale From Polypropylene and Copper Tubes
J. Sol. Energy Eng. -- February 2010 -- Volume 132, Issue 1, 011013 (9 pages)
doi:10.1115/1.4000573
You are not logged into the ASME Digital Library.
Log in
This paper presents an analytical model and an experimental study of adhesion and fluid shear removal of calcium carbonate scale on polypropylene and copper tubes in laminar and turbulent water flows, with a view toward understanding how scale can be controlled in solar absorbers and heat exchangers. The tubes are first coated with scale and then inserted in a flow-through apparatus. Removal is measured gravimetrically for Reynolds numbers from 525 to 5550, corresponding to wall shear stresses from 0.16 Pa to 6.0 Pa. The evolutionary structure of the scale is visualized with scanning electron microscopy. Consistent with the predictive model, calcium carbonate is more easily removed from polypropylene than copper. In a laminar flow with a wall shear stress of 0.16 Pa, 65% of the scale is removed from polypropylene while only 10% is removed from copper. Appreciable removal of scale from copper requires higher shear stresses. At Reynolds number of 5500, corresponding to a wall shear stress of 6.0 Pa, 30% of the scale is removed from the copper tubes. The results indicate scale will be more easily removed from polypropylene, and by inference other polymeric materials, than from copper by flushing with water.
©2010 American Society of Mechanical Engineers
| History: | Received 9 August 2009; revised 16 September 2009; published 4 January 2010 | |